Approvals/certifications |
Certified to EN54-3 & 23 by the LPCB & VdS. |
Protocol/compatibility |
Compatible with C-TEC’s CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on third-party panels is recommended before use) |
Application/operation |
Designed to be ceiling mounted – either stand-alone with a red or white cap or as part of a stacked Sounder/VAD/Detector Base combination. |
VAD category & coverage |
O-R-3-2.5-17 Rectangular coverage – ideal for corridor spaces. |
Flash rate & colour |
0.5Hz; 1Hz or OFF / White. |
Supply/operating voltage |
18 to 30V DC. |
Nominal SPL (Sound Pressure Level) |
96dB(A). |
Alarm current |
At 30Vdc: 12.2mA (0.5Hz) or 19.5mA (1Hz); At 18Vdc: 14.5mA (0.5Hz) or 25mA (1Hz) |
Product dimensions (mm) |
122mm diameter x 46mm deep (not including optional detector and base). |
IP Rating |
IP21C (Type A). |
Weight |
170g. |
Operating conditions/temperature |
-10ºC to +55ºC. Max. 95% RH (Non-condensing). |
Notes |
For compliance to EN54-3 & EN54-23, the BF431QCP Quick Connect Plate must be used with the base device. |