{"id":5571,"date":"2021-05-23T15:59:25","date_gmt":"2021-05-23T15:59:25","guid":{"rendered":"https:\/\/safetechhub.com\/?post_type=product&p=5571"},"modified":"2022-05-31T14:16:14","modified_gmt":"2022-05-31T14:16:14","slug":"24v-5a-encased-switch-mode-psu-to-en54-4-a2-part-no-bf562-5-e","status":"publish","type":"product","link":"https:\/\/safetechhub.com\/product\/24v-5a-encased-switch-mode-psu-to-en54-4-a2-part-no-bf562-5-e\/","title":{"rendered":"C-TEC 24V 5A Encased Switch Mode PSU to EN54-4\/A2 Part No.\u00a0BF562-5\/E"},"content":{"rendered":"

PSU CUSTOMISATION<\/strong><\/p>\n

The BF562-5\/E can be optionally customised to suit your exact requirements using a BF423 configurator and PC. Configurable parameters include\u00a0Float voltage temperature compensation; Battery charge rate (mA); Battery impedance; Input\/Output\u00a0settings.<\/p>\n

PSU STATUS LED\u00a0<\/strong>(located on the PSU PCB)<\/p>\n

1 flash = Mains Failure.<\/p>\n

2 flashes = Battery Voltage Low.<\/p>\n

3 flashes = Battery Voltage Critical.<\/p>\n

4 flashes = Charger Failure.<\/p>\n

5 flashes = Charger OK (Battery is either actively charging, or in float charge).<\/p>\n

6 flashes = No Batteries Fitted (indicating DIP Switch 4 position).<\/p>\n

7 flashes = Battery Resistance Fault (Level set by DIP Switch 2 position).<\/p>\n

8\u00a0flashes\u00a0= Output Over Voltage.<\/p>\n

\n
\n
\n

BATTERY FAULT MONITORING<\/strong><\/p>\n

The BF562-5\/E monitors battery resistance to the requirements of EN54-4\/A2. The fault threshold is directly related to the ability of the battery to deliver the rated current to the load. For example, batteries stored uncharged for long periods, during shipment and\/or distribution, degrade leading to increased internal resistance. If a degraded battery is fitted, a fault will be shown by the PSU as mandated by EN54-4\/A2.<\/p>\n

DATA PORT<\/strong><\/p>\n

Data on the BF562-5\/E’s status can be extracted from the PSU’s\u00a0bi-directional data port. The data available\u00a0includes thermistor measurements; battery terminal voltage; system voltage at load terminals; battery charge current; load current; battery impedance\u00a0and\u00a0ASCII text string status messages. Extracting this data requires additional equipment and permissions – contact C-TEC for details.<\/p>\n<\/div>\n<\/div>\n<\/div>\n","protected":false},"excerpt":{"rendered":"