{"id":5571,"date":"2021-05-23T15:59:25","date_gmt":"2021-05-23T15:59:25","guid":{"rendered":"https:\/\/safetechhub.com\/?post_type=product&p=5571"},"modified":"2022-05-31T14:16:14","modified_gmt":"2022-05-31T14:16:14","slug":"24v-5a-encased-switch-mode-psu-to-en54-4-a2-part-no-bf562-5-e","status":"publish","type":"product","link":"https:\/\/safetechhub.com\/product\/24v-5a-encased-switch-mode-psu-to-en54-4-a2-part-no-bf562-5-e\/","title":{"rendered":"C-TEC 24V 5A Encased Switch Mode PSU to EN54-4\/A2 Part No.\u00a0BF562-5\/E"},"content":{"rendered":"
PSU CUSTOMISATION<\/strong><\/p>\n
The BF562-5\/E can be optionally customised to suit your exact requirements using a BF423 configurator and PC. Configurable parameters include\u00a0Float voltage temperature compensation; Battery charge rate (mA); Battery impedance; Input\/Output\u00a0settings.<\/p>\n
PSU STATUS LED\u00a0<\/strong>(located on the PSU PCB)<\/p>\n
1 flash = Mains Failure.<\/p>\n
2 flashes = Battery Voltage Low.<\/p>\n
3 flashes = Battery Voltage Critical.<\/p>\n
4 flashes = Charger Failure.<\/p>\n
5 flashes = Charger OK (Battery is either actively charging, or in float charge).<\/p>\n
7 flashes = Battery Resistance Fault (Level set by DIP Switch 2 position).<\/p>\n
8\u00a0flashes\u00a0= Output Over Voltage.<\/p>\n
\n
\n
\n
BATTERY FAULT MONITORING<\/strong><\/p>\n
The BF562-5\/E monitors battery resistance to the requirements of EN54-4\/A2. The fault threshold is directly related to the ability of the battery to deliver the rated current to the load. For example, batteries stored uncharged for long periods, during shipment and\/or distribution, degrade leading to increased internal resistance. If a degraded battery is fitted, a fault will be shown by the PSU as mandated by EN54-4\/A2.<\/p>\n
DATA PORT<\/strong><\/p>\n
Data on the BF562-5\/E’s status can be extracted from the PSU’s\u00a0bi-directional data port. The data available\u00a0includes thermistor measurements; battery terminal voltage; system voltage at load terminals; battery charge current; load current; battery impedance\u00a0and\u00a0ASCII text string status messages. Extracting this data requires additional equipment and permissions – contact C-TEC for details.<\/p>\n<\/div>\n<\/div>\n<\/div>\n","protected":false},"excerpt":{"rendered":"
\n
\n
\n
\n
\n
\n
\n
\n
\n
A\u00a0powerful switch mode\/digital hybrid PSU that can be customised to suit your exact requirements – see\u00a0More Information<\/strong>\u00a0tab for details.<\/li>\n
Plastic\u00a0cover\u00a0on PSU PCB guards against touching live parts (to VDE 0100-410).<\/li>\n
Includes the same electronics as our BF562-5 LPCB\/VDS certified EN54-4\/A2 boxed 24V 5A PSU.<\/li>\n
Metal base plate\u00a0facilitates\u00a0straightforward\u00a0mounting\u00a0inside third-party OEM\u00a0enclosures.<\/li>\n
Includes a single-pole volt-free changeover relay that switches for any fault condition.<\/li>\n
Includes a\u00a0fault type\u00a0& hazardous voltages present LED.<\/li>\n
Two selectable battery charge currents.<\/li>\n
Battery fault impedance limits can be optimised to suit load current (helps extend battery life)*.<\/li>\n
Mains fail simulation mode.<\/li>\n
Improved on-board temperature sensor with optional remote sensor.<\/li>\n
Electronic functions comply with EN50131-6 grades 1-4 for security applications.<\/li>\n<\/ul>\n