Power requirements |
21-28VDC (200mA electronic fuse). |
Quiescent current |
7mA. |
Auxiliary inputs |
Three: (1) Hold; (2) Abort; (3) Mode. A 6k8 EOL resistor must be fitted across the terminals of the last device on each monitored input circuit. Unused circuits must have the 6k8 resistor fitted at the terminals. |
Indicators |
Gen. fire; Fire Zones (x3); Gen. disablement; Hold; 1st Stage Output; 2nd Stage Output; Release Imminent (x2); Exting. Released; Abort; Gen. Fault; Man. Only; Man/Auto. |
Controls |
Extinguishant release (housed in yellow casing); Operation keyswitch (Manual only or Manual & Auto). |
Product dimensions (mm) |
175 W x 250 H x 70 D mm. Hole required for flush mounting 156 W x 232 H x 51 D mm. |
Construction & finish |
Metal. |
IP Rating |
IP30. |
Weight |
1.338kg.. |
Operating conditions/temperature |
-5ºC to +40ºC. Max relative humidity: 95%. |
Network specification |
RS485; Max. 8 remote status units (any mix) per EP203; Four wire connection (2 power, 2 data); Daisy-chain wiring |